ION 7500 / ION 7600 User’s Guide Creating a Front Panel Reset
Chapter 2 - Using The Front Panel Page 47
These are the External Pulse modules that you can trigger from the front panel:
Refer to “Meter Resets” on page 43 for more details about the User Resets screen
in the meter’s front panel Setup menu.
To access the External Pulse modules (#4 or #6) using Designer:
1. Double-click on the Advanced Setup folder in the main meter configuration
screen. A number of framework folders appear.
2. Double-click on the folder labeled Custom Resets. The appropriate External
Pulse module is now available for your customization.
Meter Type External Pulse Modules User Resets Setup Menu Labels
ION 7500 #4 and #6
Custom 1 Trg
and
Custom 2 Trg
ION 7600 #6 Custom 1 Trg
Przeglądanie stron 46